Aercon Type LF Stabilisers .


Range

Modular air pressure of single & multi-bladed stabilisers for mounting in walls and doors. 

50LF range suitable for door mounting and 50 - 79mm thick walls. 

80LF range for walls of 80 - 99mm thick. 

100LF range for walls of 100mm and greater.

100LF Packaged fire rated stabilisers.

100LF Fire Duct Stabilisers.

LF Combined Smoke/fire rated stabilisers.

100LF Smoke/Fire Duct Stabilisers.

Stabilisers available with

anti-microbial coating



Principal features


Ideal for use in hospital operating theatres designed to HTM 03-01 or HTM 2025.

Screw fix front and rear flanges with made to measure rear slip-over flanges to suit your wall thicknesses.

Body materials - RAL 9016 white polyester coated carbon steel with other colours available on request.

Available with SteriTouch antimicrobial coating to reduce MRSA and E-Coli 157 bacteria.

Grades 304 or 316 stainless steel bodies and slip-over rear flanges.

Blades and internal parts - Grade 304 stainless steel as standard.

Blades pivot on sealed for life ball bearings.

Control of pressures from 5 - 50 Pa with an accuracy of +/- 1 Pa over the operating range.

Site adjustable. An on site commisioning service is available. 

Back to top

 

50LF Stabilisers




50LF Stabiliser dimensions


Stabilser /
blade length
No. of
blades
A
Overall Height
B
Overall Width
Aperture
width x height
50LF 300 - 550/1
1
150
Blade length + 68
B/L + 40 x 100
50LF 300 - 550/2
2
238
Blade length + 68
B/L + 40 x 188
50LF 300 - 550/3
3
326
Blade length + 68
B/L + 40 x 276
50LF 300 - 550/4
4
414
Blade length + 68
B/L + 40 x 364

50LF Stabiliser selection procedure

50 LF
flow factor table
Pressure Pa Flow factor
5 0.021
8 0.028
10 0.032
11 0.034
14 0.039
15 0.040
20 0.048
22 0.050
25 0.052
30 0.058
32 0.062
35 0.068
40 N/A
45 N/A
50 N/A

To select the appropriate 50LF stabiliser for your application:

Determine operating pressure in the range 5 - 35 Pa

Select the flow factor from the table opposite

Divide the flow in m3/s by the flow factor.

Multiply the answer by 320 to give the required total blade size in linear millimetres

Divide the total by 1, 2, 3 or 4 as appropriate to give individual blade size.

Standard blade lengths - 300, 320, 380, 460, 520 or 550 mm.

Example - 0.14 m3/s @ 22 Pa. Flow factor = 0.050 (from table)

0.14/0.050 x 320 = 896 (theoretical length of blade in mm)
As this is greater than the largest single blade, divide by 2 and round up to the nearest standard blade f
rom the blade lengths above, to give a 50LF 460/2 stabiliser (920 mm of blade.)


Back to top

80LF Stabiliser dimensions




Stabilser /
blade length
No. of
blades
Overall Height
Overall Width
Aperture
width x height
80LF 300 - 610/1
1
178
Blade length + 80
B/L + 40 x 116
80LF 300 - 610/2
2
282
Blade length + 80
B/L + 40 x 220
80LF 300 - 610/3
3
386
Blade length + 80
B/L + 40 x 324
80LF 300 - 610/4
4
490
Blade length + 80
B/L + 40 x 428

80LF Stabiliser selection procedure

80 LF
flow factor table
Pressure Pa Flow factor
5 0.041
8 0.046
10 0.051
11 0.053
14 0.062
15 0.065
20 0.076
22 0.079
25 0.083
30 0.090
32 N/A
35 N/A
40 N/A
45 N/A
50 N/A

To select the appropriate 80LF stabiliser for your application:

Determine operating pressure in the range 5 - 30 Pa

Select the flow factor from the table opposite

Divide the flow in m3/s by the flow factor

Multiply the answer by 320 to give the required total blade size in linear millimetres

Divide the total by 1, 2, 3, or 4 as appropriate to give individual blade length.

Standard blade lengths - 300, 330, 380, 430, 520, 550 or 610 mm.

Example - 0.22 m3/s @ 22 Pa. Flow factor = 0.079 (from table)
 

0.22/0.079 x 320 = 891 (theoretical length of blade in mm)
As this is greater than the largest single blade, divide by 2 and round up to the nearest standard blade f
rom the blade lengths above, to give a 80LF 470/2 stabiliser (940 mm of blade.)


Back to top

100LF Stabiliser dimensions 




Stabilser /
blade length
No. of
blades
A
Overall Height
B
Overall Width
Aperture
width x height
100LF 250 - 750/1
1
218
Blade length + 100
B/L + 40 x 136
100LF 250 - 750/2
2
342
Blade length + 100
B/L + 40 x 260
100LF 250 - 750/3
3
466
Blade length + 100
100LF 250 - 750/4
4
590
Blade length + 100
B/L + 40 x 508

100LF 250 - 750/5

5
714
Blade length + 100
B/L + 40 x 632

100LF 250 - 750/6

6

838

Blade length + 100


100LF Stabiliser selection procedure


100 LF
flow factor table
Pressure Pa Flow factor
5 0.042
8 0.053
10 0.059
11 0.062
14 0.071
15 0.073
20 0.084
22 0.089
25 0.094
30 0.103
32 0.106
35 0.112
40 0.121
45 0.131
50 0.140

To select the appropriate 100LF stabiliser for your application:

Determine operating pressure

Select the flow factor from the table opposite

Divide the flow in m3/s by the flow factor

Multiply the answer by 320 to give the required total blade size in linear millimetres

Divide the total by 1, 2, 3, 4, 5 or 6 as appropriate to give individual blade length.

Standard blade lengths :- 200, 250, 260, 300, 330, 380, 430, 470, 520, 550, 610, 650, 680, 720, or 750 mm.

Example - 0.22 m3/s @ 22 Pa. Flow factor (from table opposite) = 0.089

Formula : 0.22/0.089 x 320 = 791 (theoretical blade length in mm)
As this is greater than the largest single blade, d
ivide by 2 and round up to the nearest standard size which will indicate a
100 LF430/2 stabiliser.


Back to top

 

100LF Fire Duct Stabilisers







LF fire-ducts are “bolt on” units fitted to the outlets of
100LF pressure stabilisers to provide 2 hour fire resistance
available with new stabilisers or for retro-fitting to existing ones.
Actionair Type 101 Fire-Shield damper with bi-metallic cassette
release.  Fire damper operates at  72 degrees Centigrade.


Stabilser  range
Blade length
Aperture width
Aperture height
LF300 - 750/1
300 - 750
Blade length + 100
218
LF300 - 750/2
300 - 750
Blade length + 100
342
LF300 - 750/3
300 - 750
Blade length + 100
466
LF300 - 750/4
300 - 750
Blade length + 100
590
LF300 - 750/5
300 - 750
Blade length + 100
714
LF300 - 750/6
300 - 750
Blade length + 100
838


Back to top


 

100LF Smoke/Fire Duct Stabilisers







LF smoke/fire-ducts are “bolt on” units fitted to the outlets of
100LF pressure stabilisers to provide 2 hour fire resistance
and full smoke protection Available for use with new stabilisers
or for retro-fitting to existing units.

Actionair 501 Smoke-Shied damper with Belimo Mode 5 or 6 actuator and
electro- thermal release mechanism set @ 72 degrees Centigrade

Stabilser  range
Blade length
Aperture width
Aperture height
LF300 - 750/1
300 - 750
Blade length + 150
406
LF300 - 750/2
300 - 750
Blade length + 150
406
LF300 - 750/3
300 - 750
Blade length + 150
530
LF300 - 750/4
300 - 750
Blade length + 150
654
LF300 - 750/5
300 - 750
Blade length + 150
778

 

Back to top



LF Fire-rate
d stabilisers


 

2 hour fire rated to BS 476 .

High finish white polyester coated carbon steel case

Clip fix egg crate outlet grille for easy access to reset fire damper.

Loose angle frames for ease of mounting.

Fire damper operates at  72oC via bi-mettalic catch.

Optional 24V AC/DC or 240V electromagnetic actuation.

LF Fire-rated stabiliser dimensions. 




Stabilser  range
Blade length
Aperture width
Aperture height
LF300 - 750/1
300 - 750
Blade length + 116
234
LF300 - 750/2
300 - 750
Blade length + 116
358
LF300 - 750/3
300 - 750
Blade length + 116
482
LF300 - 750/4
300 - 750
Blade length + 116
606
LF300 - 750/5
300 - 750
Blade length + 116
730

Back to top



LF Combined Smoke-Fire stabilisers


 

Now reduced in depth.

Whole assembly 2 hour fire rated to BS 476. High finish white polyester coated steel case. Clip fix egg crate outlet grille for easy access to smoke damper. Loose angle frames for ease of mounting. Silent closure Actionair Type 501 PTC smoke damper. Mode 5 (24V AC/DC) or Mode 6 (240V AC) Belimo motor actuation. Electro-thermal release mechanism set @ 72oC



 